EXTERNAL BATTERY(外接电池): 274V/25A
INPUT(输入交流电压): 176-276V~ 50Hz 29.6A MAX
OUTPUT(输出交流电压): 220V~ 50Hz 27.3A MAX
6KVA COS∮=0.7
INPUT BREAKER: 30A/250V
OUTPUT BREAKER: 30A/250V
Santak CASTLE Series 6K, 10K UPS make use of the unique AC-DC conversion circuitry to detect the electricity current and voltage output of utility power supply. The current is input via the high frequency PWM to maintain uniform wave form and phase in line with the voltage, so as to attain high input power factor over 95% and avoid generating comparatively significant harmonic interference on the power network. It can be placed in the computer room next to other computer equipment. The on-line sine wave design of Santak CASTLE Series 6K, 10K UPS are suitable for all high precision equipment in the computer room. With normal utility power supplied via the AC-DC circuit, the DC bus voltage is obtained and then the inverter converts the DC bus into 220V AC output. Therefore, the power used by the load is a purified sine wave power of regulated voltage and regulated frequency with noisy signals filtered. With the use of the outstanding IGBT as the power conversion component, the operating frequency of the inverter of UPS is capable of reaching tens of KHz, due to the high frequency operating characteristics of IGBT. Higher working efficiency of the inverter also improves the overall efficiency of UPS. Moreover, higher inversion frequency reduces the noise of the inverter as well. As a result, the placement of 'CASTLE' Series UPS right in the computer room will not affect your work.
Key FeaturesRS232 communication port Connection of Santak Power Management software for power detection and monitoring via RS232 digital communication port enables direct on-screen monitoring of the status of power supply and UPS, so as to simplify the network management work and improve the reliability of computer system. |
Centralized control
front panel The easy-to-read display of the centralized control lets you know at one glance the operation and the load status of UPS as well as the power supply status of the battery etc. In other words, you will be able to monitor the power supply quality of UPS and any change of the application environment at any time. |
Automatic detection When the UPS is powered on, it immediately performs an inspection of the components such as the inverter and the battery as well as the load, so as to detect any problem in time to avoid causing any negligence or loss. |
Self-protection Equipped with the comprehensive self-protection design, no matter whether UPS is overloaded or short circuited, or the battery voltage is excessively low, or the temperature of UPS is too high, the UPS will be switched off automatically. |
Remote monitoring The UPS is equipped with an Intelligent Slot (SNMP slot) to allow communication among various operation systems and remote monitoring of the UPS. |
Alarm silence The real-time alarm silencing function eliminates the unnecessary and annoying noises. |
DC Power-on/Power-off The unique DC power-on function elaborates the emergency standby capability of UPS to a sufficient extent. |
Product |
Castle |
|
Model |
C6K |
|
Rated Power |
Volt-Amps/Watts (VA/W) |
6KVA/4.2KW |
Input |
Nominal Voltage |
220Vac |
Voltage Window |
176 ~ 276Vac |
|
Frequency Range |
46.5Hz ~ 55Hz |
|
Phase |
Single phase with ground |
|
Current (A) |
24A (30A max.) |
|
Power Factor |
0.97 |
|
Output |
Voltage |
220Vac +/-3% |
Frequency |
50Hz +/-0.5% (Battery mode) |
|
Wave-form |
Sine wave |
|
Power factor |
0.7 |
|
Distortion |
< 5% |
|
Overload Capability |
105~130% for 10 min., 130% for 1 sec. (Line mode) |
|
Current Crest Ratio |
3:1 max. |
|
Battery |
Type |
Sealed Lead-Acid, Maintenance free (Panasonic) |
Capacity |
Twenty 12V7.0Ah |
|
Back-up time (Full load) |
8 min |
|
Recharge time |
8 hrs to 90% of full capacity after full load discharge |
|
Transfer time |
0 |
|
LED indicators |
Status |
Load level/Battery level, Battery, Utility power, Inverter, Bypass, Overload, Fault |
Audible alarm |
Battery mode |
Alarm beeps every four seconds, every second if battery discharge near ending |
Overload |
Alarm beeps two for every second |
|
Fault |
Alarm beeps continuously |
|
Acoustic noise |
At 1 meter distance |
< 55 dBA |
Communications |
DB-9 Port |
RS-232 Serial Interface; Power monitoring and unattended System(s) shutdown via WinPower software |
Intelligent Slot (SNMP) |
Power Management from SNMP manager and Web browser via WebPower (Option) |
|
Weight |
Unit |
89 Kg |
Shipping |
92 Kg |
|
Dimensions |
Unit |
260 x 555 x 710 mm |
Shipping |
465 x 842 x 990 mm |